Cooling Water Chemical Dosing Skid
Multi-Chemical Dosing System for Cooling Tower Scale, Corrosion, and Biofouling Control
The TL-DS-CW is a multi-pump chemical dosing skid designed for cooling water treatment programs. The system simultaneously doses scale inhibitor, corrosion inhibitor, biocide, and dispersant at independently controlled rates, with online monitoring of conductivity, pH, and ORP to optimize chemical consumption and maintain system efficiency.
Product Overview
Cooling water systems are susceptible to scale deposition, corrosion, and biological fouling — all of which reduce heat transfer efficiency and increase energy consumption. A properly designed chemical treatment program requires precise, independent dosing of multiple chemicals at controlled concentrations. The TL-DS-CW skid integrates all dosing functions into a single, compact unit with centralized monitoring and control.
Working Principle
The skid incorporates 2–4 independent metering pumps, each connected to a dedicated chemical tank (scale inhibitor, corrosion inhibitor, biocide, dispersant). Each pump is controlled independently: scale inhibitor and corrosion inhibitor are typically dosed proportionally to make-up water flow (via a 4–20 mA signal from the make-up water meter); biocide is dosed on a timer-based shock dosing schedule; dispersant is dosed continuously at a low rate. Online sensors (conductivity, pH, ORP) monitor the cooling water quality and trigger automatic blowdown or chemical dosing adjustments.
Technical Specifications
| Parameter | Value |
|---|---|
| Number of Dosing Pumps | 2–4 (configurable) |
| Pump Capacity (each) | 0–50 L/h (standard) |
| Tank Volume (each) | 100 L / 200 L PE |
| Online Sensors | Conductivity, pH, ORP (standard); Cl₂ optional |
| Control Mode | Timer / Proportional (flow-based) / Sensor-based |
| Blowdown Control | Automatic conductivity-based blowdown valve control |
| Power Supply | 220V AC / 380V AC, 50 Hz |
| Protection Rating | IP55 |
| Communication | RS485 Modbus RTU; 4–20 mA |
| Skid Dimensions | Customized (typically 1.5 × 0.8 × 1.8 m) |
Typical Applications
Frequently Asked Questions
Related Products



Ready to Specify the Cooling Water Chemical Dosing Skid?
Our engineers will review your process parameters and recommend the optimal model, tank volume, and control configuration for your application.